Answer:
The correct answer is E. 25 amp, 2-pole
Explanation:
In United States, the mains voltage is 120 Volts at 60 Hz, Single Phase (One Hot Leg).
Firstly, as the resistive heater requires 240 Volts therefore 2 hot wires/ 2 phase will be used with single neutral wire. Hence, 2 pole breakers will be required.
Secondly, the ampere rating of breakers is selected with 25 % overload capacity as per NEC standards. Therefore, 18 x 1.25 = 22.5 A.
According the calculations and as per available options, 25 A, 2 pole breaker is selected.